a) 电流元件整定范围:1.0A~100.0A,级差0.1A,误差不超过±5%;
b) 时间元件整定范围:Ⅰ段:0.00s~20.00s,Ⅱ、Ⅲ段:0.10s~20.00s,级差0.01s,误差不超过±1%或±40ms,过流加速:0.00s~10.00s,级差0.01s,误差不大于±1%或±45ms;
c) 方向元件:误差不大于±5°;
d) 低电压启动元件整定范围:60.0V~100.0V,级差0.1V,误差不超过±5% 。
a) 过负荷电流整定范围:0.5~25.0A,级差0.1A,误差不超过±5%;
b) 时间元件整定范围:0.10s~90.00s,级差0.01s,误差不超过±1%或±40ms。
a) 重合闸延时整定范围:0.2~20.00s,级差0.01s,误差不超过±1%或±50ms;
b) 重合闸同期角整定范围:5.0~50.0°,级差0.1°,误差不超过±5°。
a) 频率定值整定范围:45.00Hz~50.00Hz,级差0.01Hz,误差不超过±0.01Hz;
b) 闭锁滑差整定范围:0.50~10.00Hz/s,级差0.01Hz/s,误差不超过±3%或±0.05Hz/s;
c) 延时时间整定范围: 0.20s~20.0s,级差0.1s,误差不超过±1%或50ms;
d) 低压闭锁整定范围:60.0~100.0V,级差0.1V,整定值误差不超过±5%;
e) 低流闭锁整定范围:0.3~5.0A,级差0.1A,误差不超过±5%或±0.05A。
a) 电流元件整定范围:0.1~10.0A,级差0.1A,误差不超过±5%;
b) 时间元件整定范围:0.10s~20.00s,级差0.01s,误差不超过±1%或±40ms;
c) 方向元件:误差不超过±5°。
a) 低电压整定范围:70.0~110.0V,级差0.1V,误差不超过±5%;
b) 低电压保护整定时间:0.10~20.00s,级差0.01s,误差不超过±1%或±40ms。
a) 过电压整定范围:90.0~140.0V,级差0.1V,误差不超过±5%;
b) 过电压保护整定时间:0.10~20.00s,级差0.01s,误差不超过±1%或±40ms。
a) 电流测量范围:0A~6A,误差不超过±0.2%;
b) 电压测量范围:0V~100V,误差不超过±0.2%;
c) 有功功率、无功功率误差不超过±0.5%;
d) 功率因数误差不超过±0.5%;
e) 频率测量范围:45Hz~55Hz,误差不超过±0.01Hz。