型号FR-A740-□□K-CHT |
0.4 |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
|||
输出 |
适用电机容量(kw)*1 |
SLD |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
- |
|
LD |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
- |
|||
ND |
0.4 |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
55 |
|||
HD |
0.2 |
0.4 |
0.75 |
1.5 |
2.2 |
3.7 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
|||
额定电流(A)*3 |
SLD |
2.3 |
3.8 |
5.2 |
8.3 |
12.6 |
17 |
25 |
31 |
38 |
47 |
62 |
77 |
93 |
116 |
- |
||
LD |
2.1 |
3.5 |
4.8 |
7.6 |
11.5 |
16 |
23 |
29 |
35 |
43 |
57 |
70 |
85 |
106 |
- |
|||
ND |
1.5 |
2.5 |
4 |
6 |
9 |
12 |
17 |
23 |
31 |
38 |
44 |
57 |
71 |
86 |
110 |
|||
HD |
0.8 |
1.5 |
2.5 |
4 |
6 |
9 |
12 |
17 |
23 |
31 |
38 |
44 |
57 |
71 |
86 |
|||
过载能力*4 |
SLD |
110% 60s,120% 3s 环境温度40℃ |
||||||||||||||||
LD |
120% 60s,150% 3s 环境温度50℃ |
|||||||||||||||||
ND |
150% 60s,200% 3s 环境温度50℃ |
|||||||||||||||||
HD |
200% 60s,250% 3s 环境温度50℃ |
|||||||||||||||||
电压*5 |
3相 380-480V 50/60Hz |
|||||||||||||||||
再生制动转矩 |
最大值·允许使用率 |
100%转矩·2� |
20%转矩·连续 适用外置制动电阻时,为100%转矩·6� |
20%转矩·连续 |
||||||||||||||
输入 |
额定输入交流电压,频率 |
3相 380-480V 50/60Hz |
||||||||||||||||
交流电压容许变动范围 |
323-528V 50/60Hz |
|||||||||||||||||
允许频率波动范围 |
±5% |
|||||||||||||||||
电源容量(KVA)*2 |
1.5 |
2.5 |
4.5 |
5.5 |
9 |
12 |
17 |
20 |
28 |
34 |
41 |
52 |
66 |
80 |
100 |
|||
保护结构 |
封闭型(IP20) |
开放型(IP00) |
||||||||||||||||
冷却方式 |
自冷 |
强制风冷 |
||||||||||||||||
大约重量(kg) |
3.8 |
3.8 |
3.8 |
3.8 |
3.8 |
7.1 |
7.1 |
7.5 |
7.5 |
13 |
13 |
23 |
35 |
35 |
37 |