序号 | 电压等级 (KV) | 电缆长度 (KM) | 选用装置型号 | 最好谐振 电压(KV) | 装置额定 电流(A) | 额定输出 容量(KVA) |
1 | 10 | 1 | YD-2000-80/40 | 40 | 2 | 80 |
2 | 2 | YD-2000-120/20 | 20 | 6 | 120 | |
3 | 3 | YD-2000-315/30 | 30 | 10.5 | 315 | |
4 | 4 | YD-2000-315/30 | 30 | 10.5 | 315 | |
5 | 5 | YD-2000-315/30 | 30 | 10.5 | 315 | |
6 | 35 | 0.5 | YD-2000-120/60 | 60 | 2 | 120 |
7 | 1 | *YD-2000-315/90 | 90 | 3.5 | 315 | |
YD-2000-210/60 | 60 | 3.5 | 210 | |||
8 | 2 | *YD-2000-630/90 | 90 | 7 | 630 | |
YD-2000-420/60 | 60 | 7 | 420 | |||
9 | 3 | YD-2000-600/60 | 60 | 10 | 600 | |
10 | 4 | YD-2000-600/60 | 60 | 10 | 600 | |
11 | 5 | YD-2000-900/60 | 60 | 15 | 900 | |
12 | 110 | 1 | YD-2000-600/120 | 120 | 5 | 660 |
YD-2000-660/110 | 110 | 6 | 550 | |||
13 | 2 | YD-2000-1320/110 | 110 | 12 | 1320 | |
14 | 3 | YD-2000-1980/110 | 110 | 18 | 1980 | |
15 | 4 | YD-2000-2640/110 | 110 | 24 | 2640 | |
16 | 5 | YD-2000-2640/110 | 110 | 24 | 2640 | |
17 | 220 | 1 | YD-2000-2000/200 | 200 | 10 | 2000 |
18 | 2 | YD-2000-4000/200 | 200 | 20 | 4000 | |
19 | 3 | YD-2000-6000/200 | 200 | 30 | 6000 | |
20 | 4 | YD-2000-8000/200 | 200 | 40 | 8000 | |
21 | 5 | YD-2000-8000/200 | 200 | 40 | 8000 |
注:(1)本装置中参数按电力试验规程中交接试验电压标准计算。
(2)交联电缆的电容值10KV电缆按每公里0.4uf计算:35KV、110KV及220KV电缆平均按每公里0.2uf计算。